Price - $3.00
INSTALLATION,
OPERATING AND SERVICE
INSTRUCTIONS FOR
V7 SERIES OIL FIRED BOILER
KNOCKDOWN & PACKAGED
HEATING UNITS
Theseinstructionshavebeen
reviewedbyULCandfound
suitable for use in the
installationofULClabeled
V-7SeriesBoilers.
As an
ENERGY
STAR® Partner,
Burnham Corporation
has determined that the
V73WR (0.60 GPH),
V74WR (0.80 GPH),
V75WR (0.90 GPH),
and V76WR (1.15 GPH)
meet the ENERGY STAR®
guidelines for Energy
efficiency established by the
United States Environmental
Protection Agency (EPA).
The ULC label or listed
marking on a product is the
onlyevidenceprovidedby
Underwriters'Laboratoriesof
Canadatoidentifyproducts
whichhavebeenproduced
underthelistingandfollow-up
service.
For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide
Boiler Model Number and Serial Number as shown on Rating Label.
Boiler Model Number
Boiler Serial Number
Installation Date
_V7 ____-____
6_ _ _ _ _ _ _
Heating Contractor
Phone Number
Address
8142711R24-7/99
IMPORTANT
Before starting to install this oil boiler, read these instructions carefully. Keep instructions in legible condition and
posted near oil boiler for reference by owner and service technician.
TABLE OF CONTENTS
I. General Information ............................. 3
II. Knockdown Boiler Assembly ............... 7
III. Installation Instructions...................... 12
IV. Operating Instructions........................ 21
V. Boiler Cleaning .................................. 29
VI. Repair Parts ........................................ 31
Burner Specifications ......................... 46
SECTION I: GENERAL INFORMATION
Figure 1A: V72 thru V79 Water Boiler Without Tankless Heater (WB)
TABLE 1: DIMENSIONAL DATA (SEE FIGURES 1A THRU 1E)
Heat Transfer
Dimensions
Water Content -
Gallons
Surface Area -
Sq. Ft.
Boiler
Model
No.
Approximate
Shipping Weight
(LB.)
Minimum
Chimney Size
Steam Water
Boiler Boiler
"A"
"B"
"C"
Steam Boiler
V72
V713
V73
V714
V74
V75
V76
V77
V78
V79
11-3/8" 6-3/8"
16" 8-3/4"
15-3/8" 8-3/8"
20" 10-3/4"
5"
6"
6"
6"
6"
7"
7"
8"
8"
8"
8" x 8" x 15'
8" x 8" x 15'
8" x 8" x 15'
8" x 8" x 15'
8" x 8" x 15'
8" x 8" x 15'
8" x 8" x 15'
8" x 12" x 15'
8" x 12" x 15'
8" x 12" x 15'
----
----
10.6
13.5
13.2
15.9
15.9
18.5
21
----
----
381
524
478
580
575
674
773
872
971
1070
10.8
----
13.8
----
19-3/8" 10-3/8"
23-3/8" 12-3/8"
27-3/8" 14-3/8"
31-3/8" 16-3/8"
35-3/8" 18-3/8"
39-3/8" 20-3/8"
13.5
16.1
18.6
21.2
23.8
26.4
19.7
25.6
31.4
37.3
43.1
49.0
23.6
26.2
28.8
NOTE: 1. Maximum Working Pressure 15 PSI (Steam) and 30 PSI (Water)
2. The V72, V713 and V714 Boilers are available as packaged water boilers only
3. The V713 and V714 are not ULC listed Models
3
Figure 1B: V73 thru V79 Water Boiler with Tankless Heater (WBT)
Figure 1C: V73 thru V79 Steam Boiler with or without Tankless Heater ("SBT" or "SB")
4
Β υρνηαµ
Figure 1D: V713 and V714 Packaged Water Boiler Less Tankless Heater (WB)
Burnham
Figure 1E: V713 and V714 Packaged Water Boiler with Tankless Heater (WBT)
5
A. INSPECT SHIPMENT carefully for any signs of
2. FOR BASEMENT INSTALLATION, provide a
solid base, such as concrete, if floor is not level, or
if water may be encountered on floor around boiler.
damage.
1. ALL EQUIPMENT is carefully manufactured,
inspected and packed. Our responsibility ceases
upon delivery of crated boiler to the carrier in good
condition.
3. PROVIDE SERVICE CLEARANCE of at least 24”
on right side of boiler for removal of rear tankless
heater. Provide at least 24” clearance from front
jacket panel for servicing and removal of front
tankless heater (increase to 30" for #A54 heater).
Provide at least 24" clearance from right side of
boiler or top of boiler for cleaning flueways. Boiler
flueways may be cleaned either from the top or
from the side.
2. ANY CLAIMS for damage or shortage in shipment
must be filed immediately against the carrier by the
consignee. No claims for variances from, or
shortage in orders, will be allowed by the
manufacturer unless presented within sixty (60)
days after receipt of goods.
4. For minimum clearances to combustible materials.
See Table 2.
B. LOCATE BOILER in front of final position before
removing crate. See Figures 1A thru 1E.
C. PROVIDE AIR SUPPLY AND VENTILATION to
accommodate proper combustion. If natural ventilation
is inadequate, provide a screened opening or duct from
the boiler room to the outside. The opening or duct
must be sized so the boiler input will not exceed 4,000
BTUH/Sq. In. of free area. If other air consuming
appliances are near the boiler, the air inlet should be
larger. Consult respective manufacturers.
1. LOCATE so that smoke pipe connection to
chimney will be short and direct. BOILER IS
SUITABLE FOR INSTALLATION ON
COMBUSTIBLE FLOOR. Boiler cannot be
installed on carpeting.
NOTE 1: Listed clearances comply with American
National Standard ANSI/NFPA 31, Installation of Oil
Burning Equipment.
TABLE 2: Minimum Installation Clearances To
Combustible Materials (Inches)
NOTE 2: V7 Series boilers can be installed in rooms
with clearances from combustible material as listed
above. Listed clearances cannot be reduced for
alcove or closet installations.
C
A
B
Chimney
D
E
Boiler Above Front
Connector
Rear Sides
NOTE 3: For reduced clearances to combustible
material, protection must be provided as described in
the above ANSI/NFPA 31 standard.
V7 24
6
18
6
6
6
SECTION II: KNOCKDOWN BOILER ASSEMBLY
Note: If Boiler is Packaged Go To Section III
section as shown in Fig. 3. Place gaskets so as not
to allow any flueway blockage.
A. REMOVAL OF BARE BOILER FROM SKID
1. Boiler is secured to base with 4 bolts, 2 on front and
2 on rear, see Figure 2. Remove all bolts.
2. Cut the remainder of the roll into two (2) equal
pieces. Place each piece along the sides, allowing
the ends to overlap the front and rear pieces.
2. Tilt boiler to right and to rear. Using right rear leg
as pivot, rotate boiler 90° in a clockwise direction,
and lower left side of boiler to floor. Tilt boiler and
remove crate skid.
Do not allow any flueway blockage.
3. Position canopy body within the retaining bar
which borders the flueway openings on top of the
bare boiler block assembly.
Figure 2
B. MOVE BOILER TO PERMANENT POSITION by
sliding or walking.
C. TEST BOILER FOR LEAKS before installing
controls, trim, and jacket, and before connecting to
heating system.
1. Loosen nuts on tie rods until only finger tight.
2. Install pressure gauge (at least 30 P.S.I. capacity), a
hose to the city water and a valve in the supply
tapping. Plug remainder of tappings.
Figure 3
3. Fill boiler with water and apply a pressure of at
least 10 pounds but no more than 30 pounds gauge
pressure.
IMPORTANT: Jacket support bracket must be
facing left side of boiler — see Figure 3.
4. Secure canopy to boiler with two (2) 1/4" - 20 x 3"
lg. carriage bolts, 1/4" flat washers and 1/4" - 20
wing nuts provided.
4. Examine Boiler carefully inside and outside for
leaks or damage due to shipment or handling.
D. DRAIN WATER FROM BOILER. Remove gauge,
valve and plugs from those tappings to be used. Leave
other tappings plugged or bushed according to Figure
4.
H. INSTALL the following steam or water trim that
would be concealed or inaccessible after flush jacket is
installed, see Figure 4 for boiler tapping locations and
usage.
E. INSPECT JOINTS BETWEEN SECTIONS. All joints
are factory sealed. If there are any spaces due to
shipment or handling, seal them with boiler putty.
1. STEAM BOILER — Top tappings:
a. Tapping "L" — Install 2" plug in rear section
top supply tapping on boiler sizes V73 thru
V75.
F. INSPECT FLUE COVER PLATES for tightness. If
loose, retighten mounting hardware. If flue plate or
sealing insulation is damaged repair or replace as
needed.
b. Tapping “M” — Install ¾” coupling and ¾” x
8” long nipple into ¾” tapping located next to
front section top supply tapping — all boiler
sizes.
G. INSTALL AND SECURE CANOPY with cerafelt
gasket and hardware provided to ensure gas tight seal
— see Figure 3.
2. WATER BOILER — Top tappings:
a. Tapping “L” — Install 2” plug in rear section
top supply tapping on boiler sizes V73 thru
V79.
1. Cut two (2) strips 13 ¾” lg. from the roll of cerafelt
gasket insulation. Place one (1) strip across the top
of the front section and the other across the rear
7
Figure 4: Boiler Tapping Locations and Usage (Knockdown Boilers Only)
PU RP OSE OF TA PP INGS
Tapping
Location
S team B oiler
Water B oiler
S ize
Non-Heater
w/Heater
Non-Heater
L81 48A
Front Heater
L81 24C
R ear Heater
Flush Plug
PA4 04A Pressuretrol (P robe LW CO )
Plugg ed (Flo at LW CO )
A
B
¾"
¼"
¾ "
¾"
½ "
Op erating C on trol Op erating C on trol
Pressure/Va cuum G auge
Temp era ture/Pre ssure G auge
Flush Plug
Pro be LWC O Std.
C
Plugged (Flo at LW CO )
C-C
D
Flush Plug
Flush Plug
Flush Plug
Water Gau ge Glass (Probe LW CO )
Flush Plug
Water G auge G lass, Pre ssuretrol, a nd LW CO (Flo at)
L4006A Op era tin g
L81 24C
Op erating C on trol
F
¾"
-----
-----
Disre gard
C on trol
G
H
J
1½"
1½"
1½"
2"
Bushe d to ¾ " for Draincock (O ptiona l Re tu rn )
R eturn
R eturn
Bushe d to ¾ " for Draincock (O ptiona l Re tu rn )
Flush Plug
Su rface Blow off - Plugged
Front Su pply (3 thru 9 Section)
K
Front Su pply (3 thru 9 Section)
Plugged , Optional Se co nd Su pply (3 thru 5 Section)
R equire d S eco nd Supply (6 thru 9 Se ction )
L
M
P
2"
Plu gge d (3 thru 9 Section)
Re lief Valve
¾"
¾"
¾"
Safety Valve
Aux. Ta pping -
Plu gged
Aux. Ta pping -
Plu gged
Au xiliary Tapp ing - Plugge d
Disre gard
R
Au xiliary Tapp ing - Plugge d
Au xiliary Tapp ing - Plugge d
8
Figure 5: Knockdown Boiler Jacket Assembly
b. Tapping “M” —Install ¾” x 8” long nipple into
side panel mounting holes with the front and rear
panel holes. Secure with #8 x ½” long sheet metal
screws.
¾” tapping located next to front section top
supply tapping — all boiler sizes.
I. INSTALL FLUSH JACKET (See Figure 5).
5. Install jacket top panel. Place jacket top panel on
boiler and secure to front, rear and left side panels
with #8 x ½” long sheet metal screws.
1. Remove burner swing door mounting plate. Loosen
the bottom bolt three full turns. Remove (5)
remaining 5/16” bolts securing mounting plate to
boiler sections.
6. Install jacket lower right side panel. Align right
side panel mounting holes with front and rear panel
holes. Secure with #8 x ½” long sheet metal screws.
Lift up and remove plate.
7. Install jacket upper right side access panel. Using
the thumb holes, hold access panel 1” above lower
right side panel. Engage flanges on access panel
with surrounding panels and lower into position
until access panel is resting flush with top panel
and bottom flange is properly locked into position
with lower right side panel.
2. Install rear jacket panel. Align two dimpled holes
on jacket panel with the cast iron lugs. Secure with
two #10 x 3/8” long self tapping screws.
3. JACKET FRONT PANEL
a. Install black plastic collar extension to jacket
front panels with 7-13/16" dia. heater opening.
Engage two (2) retaining tabs over raw edge of
opening. Provide support behind the panel with
one hand while applying pressure on collar to
snap each tab over edge of opening until all
eight (8) tabs are securing collar.
8. Attach the data labels shipped in the instruction
envelope as follows: (see Figure 5).
a. Place the Rating Label (serialized)
approximately 1/4" below the top edge and
3-1/2" from the right edge of the jacket front
panel as shown. Mark outline of label on jacket
with a pencil. Remove paper backing from
label, realign label with pencil marks and apply
label to jacket by using backing paper to rub
across face of label.
b. Install front jacket panel. Locate two 3/16”
diameter holes on front panel approximately 16”
up from the bottom of the panel and 4½” in
from each side. Align these holes with the
similarly located cast iron lugs on the front
section. Secure with two #10 x 3/8” long self-
tapping screws.
b. Locate the Combination Label (P/N 8142756)
on the front right corner of top panel,
4. Install jacket left side panel. Fold panel at
perforation keeping insulation inward. Align left
approximately 3/8" from each edge as shown.
Mark the location and apply label in the same
9
Figure 6
manner as rating label.
burner to the left. Install two remaining 5/16” x ½”
long bolts in horizontal sets of holes. Level burner
and fully tighten all bolts.
c. On steam boilers, install the Lowest Permissible
Water Level Plate, Form No. 1204 (shipped in
Steam Trim Carton), on the jacket right side
panel. Align the two holes in the plate with the
two 1/8” dia. holes located near the front edge,
in line with the lower sight glass tapping, and
secure with #8 x ½” lg. sheet metal screws.
K. INSTALL STEAM BOILER TRIM AND CONTROLS
(See Figures 1C & 4).
1. Thread the combination pressure/vacuum gauge
into the ¼” tapping. Tighten with wrench applied
to the square shank of the gauge. Do not apply
pressure to the gauge case — this might destroy the
calibration of the gauge.
J. INSTALL OIL BURNER (See Figure 6).
1. Check target wall and cerafelt blanket in
combustion chamber. If any damage or movement
occurred during shipment, repair or replace as
needed.
2. Thread 1½” x ¾” bushing and a ¾” drain cock into
the 1½” tapping located in the lower right corner of
the front casting. Tighten with wrench.
2. Check the burner mounting plate and swing door
insulation pieces for damage and adhesion. If
damaged, replace insulation. If loose, re-attach with
RTV 732 or 736 silicone caulk.
NOTE: Lower rear section tapping “H” is used for
standard condensate return on steam boilers.
3. Thread safety relief valve, as shown in Figure 1C,
into 3/4" coupling and 3/4” x 8” nipple previously
installed in step H. Tighten with wrench.
3. Engage bottom slot on burner mounting plate with
matching bolt in bottom tapping of front section.
Align mounting holes and fasten the mounting
plate to the boiler sections with (5) five 5/16” bolts
and washers removed in step 8a. Fully tighten all
bolts.
NOTE: Pipe discharge as shown in Figure 8.
4. Install probe type LWCO if so equipped. Thread
probe into ¾” tapping located on the front section
directly above the protectorelay on the oil burner.
Read the manufacturer’s instructions packed with
the probe LWCO for proper pipe dope application.
DO NOT use Teflon tape on probe threads. Use of
teflon can render the probe LWCO inoperational.
Slip the LWCO control over the probe and clamp in
place. Connect the wire(s) between the probe and
control per the manufacturer’s instructions. Install
4. Place burner flange gasket on burner swing door
and thread two 5/16” x ½” long bolts into vertical
set of holes approximately three full turns.
5. Insert oil burner air tube into the opening of the
burner swing door. Align keyhole slot with vertical
set of bolts, engage hex head of bolts and rotate
10
the sight glass using the two ½” tappings to the
right of the probe LWCO.
4. Screw drain valve into 1½” tapping in lower rear
section using 1½” x ¾” bushing (note - lower front
section tapping “G” (see Figure 4) is used for
standard return on water boilers).
5. Install float-type Low Water Cutoff, if so equipped.
See Figure below.
5. If CIRCULATOR (not supplied with boiler) is to be
mounted directly to 1½" boiler return tapping "G",
use the piping arrangements outlined in steps a. thru
e. as follows:
a. Install nipples and unions in Tappings D.
b. Mount hardware to low water cutoff body. Install
assembly.
c. Install water gage glass on low water cutoff
assembly's tee fittings.
a. Thread 1½” x 3” long nipple and 1½” x 90°
elbow into the return tapping and tighten with a
pipe wrench.
6. Install Limit Control.
a. Probe LWCO: Install Limit in Tapping A using
¾ NPT x 2" nipple, ¾ NPT elbow, ¾ NPT x ¼
NPT bushing, and syphon. See Figure below
right.
b. Float LWCO: Remove ¼ NPT plug from top of
Low Water Cutoff. Install Syphon and Limit into
this tapping. See Figure below.
b. Thread 1½” NPT x 15” long pipe nipple into the
90° elbow and tighten with a pipe wrench.
c. Thread one of the circulator flange onto the pipe
nipple and tighten with a pipe wrench. Position
flange so that the bolt slots are perpendicular to
the boiler front.
7. On units equipped with a tankless heater, install the
aquastat controller well in the ¾” tapping in tankless
heater plate. Slip the bulb of the aquastat into the well
and secure the control in place with the set screw.
d. Place a flange gasket in the flange groove on the
circulator and mount the circulator on the flange
installed in step 3. Note that this is the return
piping and the flow arrow on the circulator should
point down ê. Fasten circulator with 7/16” nuts
and bolts.
8. Connect the field wiring to the pressure limit, the
LWCO, the burner J-box, and from the aquastat
control (if equipped with tankless heater) to the oil
burner primary control's "T-T" terminals. Make the
wiring connections as shown in Figures 17 thru 20.
e. Bolt second circulator flange and gasket to the
circulator with 7/16” nuts and bolts.
6. Install pressure relief valve, as shown in Figure 1B,
onto ¾” x 8” nipple previously installed in Step H.
Tighten with wrench.
L. INSTALL WATER TRIM AND CONTROLS
(See Figures 1B and 4).
1. Thread ½” pipe plugs into gauge glass tappings in
the upper right side of front section.
NOTE: Pipe discharge as shown in Figure 9.
7. On units without a tankless heater, install the control
well into the ¾” tapping located on the front of the
boiler in the upper left corner. Tighten the well and
insert the control’s bulb into the well. Secure the
control with set screw on the control.
2. Thread ¾” pipe plug in probe low water cut off
tapping (just left of gauge glass tappings).
3. Thread combination pressure/temperature gauge into
¼” tapping. Tighten with wrench applied to the
square shank of the gauge. Do not apply pressure to
the gauge case - this might destroy the calibration of
the gauge.
8. On units with a tankless heater, install the control
well in the ¾” tapping on the tankless heater plate.
Tighten the well and insert the control’s bulb into the
well. Secure the control with set screw on the control.
9. Connect the field wiring from the circulator to the
control and from the control to the burner J-Box.
Make the wiring connections as shown on Figures 21
and 22.
NOTE: Proceed to Installation Instructions Section
III, step E, to continue.
Limit Installation for Probe LWCO Equipped
Boilers
Float-type Low Water Cutoff Installation
11
SECTION III: INSTALLATION INSTRUCTIONS
4. Packaged boilers with Probe style LWCO. Install
A. REMOVE CRATE — (Packaged Boilers)
Limit in Tapping A using ¾ NPT x 2" nipple, ¾
NPT elbow, ¾ NPT x ¼ NPT bushing, and syphon
included in trim bag. See Figure on previous page.
Connect wiring harness from Low Water Cutoff.
See Figure below.
1. Remove all fasteners at crate skid.
2. Lift outside container and remove all other inside
protective spacers and bracing. Remove draft
regulator box and miscellaneous trim bag
containing safety/relief valve, and pipe fittings.
B. REMOVAL OF BOILER FROM SKID
TS-39-126-A
5. If this boiler is used in connection with
refrigeration systems, the boiler must be installed so
that the chilled medium is piped in parallel with the
heating boiler using appropriate valves to prevent
the chilled medium from entering the boiler, see
Figure 10. Also consult I = B = R Installation and
Piping Guides.
TS-39-26-A
Fig. 7
6. If this boiler is connected to heating coils located in
air handling units where they may be exposed to
refrigerated air, the boiler piping must be equipped
with flow control valves to prevent gravity
circulation of boiler water during the operation of
the cooling system.
1. Boiler is secured to base with 4 bolts, 2 on left side
and 2 on right side, see Figure 7. Remove all bolts.
2. Tilt boiler to right and to rear. Using right rear leg
as pivot, rotate boiler 90° in a clockwise direction,
and lower left side of boiler to floor. Tilt boiler and
remove crate skid. Care should be exercised to
prevent damage to jacket or burner.
7. Use a boiler bypass if the boiler is to be operated in
a system which has a large volume or excessive
radiation where low boiler water temperatures may
be encountered (i.e. converted gravity circulation
system, etc.).
C. MOVE BOILER TO PERMANENT POSITION by
sliding or walking.
D. INSPECT COMBUSTION TARGET WALL AND
COMBUSTION CHAMBER LINER
Remove the circulator and install a pipe tee
between the circulator and boiler return along with
a second tee in the supply piping as shown in
Figure 11. The bypass should be the same size as
the supply and return lines with valves located in
the bypass and supply outlet as illustrated in Figure
11 in order to regulate water flow for maintenance
of higher boiler water temperature.
1. OPEN FLAME OBSERVATION DOOR AND/OR
BURNER SWING DOOR on front of boiler. Use
flashlight to inspect target wall secured to rear
section with silastic sealant. Inspect ceramic fiber
blanket secured to floor of boiler with water glass
adhesive. If either is damaged they must be
replaced.
E. CONNECT SUPPLY AND RETURN PIPING TO
Set the by-pass and boiler supply valves to a half
throttle position to start. Operate boiler until the
system water temperature reaches its normal
operating range.
Adjust the valves to maintain 180°F boiler water
temperature. Adjust both valves simultaneously.
Closing the boiler supply valve and opening the by-
pass valve will raise the boiler water temperature
and lower the supply temperature. Opening the
boiler supply valve while closing the by-pass valve
will lower the boiler water temperature and raise
the supply temperature.
HEATING SYSTEM.
CLEARANCES — Steam and hot water pipes shall
have clearances of at least ½” from all combustible
construction.
1. With STEAM HEATING, see Figure 8. Consult I =
B = R Installation and Piping Guide No. 200.
2. With Forced Circulation HOT WATER HEATING,
see Figure 9. Consult I = B = R Installation and
Piping Guide No. 200.
3. Packaged boilers. Install Safety Valve in Tapping
M. Use ¾ NPT x 8" nipple and ¾ NPT coupling
included in trim bag. Safety Valve must be
installed with spindle in vertical position.
8. A hot water boiler installed above radiation level
must be provided with a low water cutoff device as
part of the installation.
12
TS-39-17-D
Fig 8: V73 Thru V79 Recommended Boiler Piping For Gravity Return Steam Boiler
TS-39-4-C
Fig. 9: V72 thru V79, V713 and V714 Recommended Boiler Piping for Series Loop Forced Hot Water System
13
In order to insure long product life, oxygen sources
should be eliminated. This can be accomplished by taking
the following measures:
1. Repairing system leaks to eliminate the need for
addition of make-up water.
2. Eliminating open tanks from the system.
3. Eliminating and/or repairing fittings which allow
oxygen absorption.
TS-O-62-B
4. Use of non-permeable materials in the distribution
system.
5. Isolating the boiler from the system water by installing
a heat exchanger.
F. CONNECT TANKLESS HEATER PIPING AS
SHOWN IN Figure 12. See Tables 3 and 3A for
Tankless Heater Ratings.
Fig. 10: Recommended Piping for Combination
Heating & Cooling (Refrigeration) Systems
Water Boilers
TS-0-63-B
TS-39-7-A
Fig. 12: Schematic Tankless Heater Piping
Fig. 11: Recommended Bypass Piping
Water Boilers
THE FOLLOWING GUIDELINES SHOULD BE FOL-
LOWED WHEN PIPING THE TANKLESS HEATER:
1. FLOW REGULATION — If flow through the
heater is greater than its rating, the supply of
adequate hot water may not be able to keep up with
the demand. For this reason a flow regulator
matching the heater rating should be installed in
the cold water line to the heater. The flow regulator
should preferably be located below the inlet to the
heater and a minimum of 3’ away from the inlet so
that the regulator is not subjected to excess
CAUTION
Oxygen contamination of boiler water will cause
corrosion of iron and steel boiler components,
and can lead to boiler failure. Burnham's
standard warranty does not cover problems
caused by oxygen contamination of boiler water.
temperatures that may occur during “off” periods
when it is possible for heat to be conducted back
through the supply line. The flow regulator also
limits the flow of supply water regardless of inlet
pressure variations in the range of 20 to 125 psi.
There are many possible causes of oxygen contamina-
tion such as:
1. Addition of excessive make-up water as a result of
system leaks.
2. Absorption through open tanks and fittings.
2. TEMPERING OF HOT WATER — Installation of
an automatic mixing valve will lengthen the
3. Oxygen permeable materials in the distribution
system.
delivery of the available hot water by mixing some
14
TABLE 3: TANKLESS HEATER DATA: Rear
Mounted Heater on Steam and Water
Boilers
WARNING
Install an automatic mixing valve at the tankless
heater outlet to avoid risk of burns or scalding
due to excessively hot water at the fixtures.
Adjust and maintain the mixing valve in
Pressure Drop
thru Heater
(PSI)
Heater Rating
(GPM)
Boiler Heater
Model
No.
accordance with the manufacturer's instructions.
Steam Water Steam Water
3. FLUSHING OF HEATER — All water contains
some sediment which settles on the inside of the
coil. Consequently, the heater should be
V713
V73
V1-2
V1-2
V1-1
V1-2
V1-2
V1-2
V1-2
V1-2
V1-2
V1-2
---
2.75
---
3.25
3
---
3.9
---
---
4.7
5.6
7.2
7.2
8
5.6
4.7
4.4
8
periodically backwashed. This is accomplished by
installing hose bibs as illustrated and allowing
water at city pressure to run into hose bib A,
through the heater, and out hose bib B until the
discharge is clear. The tees in which the hose bibs
are located should be the same size as heater
connections to minimize pressure drop.
3.5
4
V714
---
V74
V75
V76
V77
V78
V79
3
3.25
3.5
3.75
4
5.6
6.4
7.2
8
3.25
3.75
3.75
4
4. HARD WATER — A water analysis is necessary
to determine the hardness of your potable water.
This is applicable to some city water and
particularly to well water. An appropriate water
softener should be installed based on the analysis
and dealer’s recommendation. This is not only
beneficial to the tankless heater but to piping and
fixtures plus the many other benefits derived from
soft water.
4.5
4.5
9.8
9.8
4
8
TABLE 3A: TANKLESS HEATER DATA: Front
Mounted Heater on Water Boilers
Boiler
Model
Heater Heater Rating
Pressure Drop
Thru Heater (PSI)
NOTE: STEAM BOILERS
No.
222
222
222
222
222
A54
222
A54
222
A54
(GPM)
a. During summertime operation, the normal water
line should be raised 1”, from 22-5/8” to
23-5/8” (see Figure 1C) for improved tankless
heater performance.
V73
V74
V75
V76
3
22
22
3.5
4
30.5
33
G. INSTALL SMOKEPIPE — The V7 should be vented
into a fireclay tile-lined masonry chimney or chimney
constructed from type L vent or a factory built chimney
that complies with the type HT requirements of
UL103. The chimney and vent pipe shall have a
sufficient draft at all times, to assure safe proper
operation of the boiler. See Figure 13 for recommended
installation.
4.5
4.6
5.5
4.75
6
33
V77
V78
V79
36
40
39.5
40
4.75
6
1. Install a draft regulator (supplied with boiler)
following the instructions furnished with the
regulator. See Figure 14 for alternate draft regulator
locations.
39.5
cold water with the hot. This prevents excessive
and possibly scalding hot water at the fixtures. In
addition, savings of hot water will be achieved
since the user will not waste as much hot water
while seeking water temperature to his liking.
Higher temperature hot water required by
dishwashers and automatic washers is possible by
piping the hot water from the heater prior to
entering the mixing valve. The mixing valve should
be “trapped” by installing it below the cold water
inlet to heater to prevent lime formation in the
valve.
2. Consider the chimney overall. Chimneys that have
a high heat loss may become less suitable as the
heat loss of the home goes down and the efficiency
of the boiler installed goes up. Most homes have a
chimney appropriate for the fuel and the era in
which the home was built. That may have been a
coal fired or an inefficient oil fired boiler built into
a home without insulation or storm windows. With
increasing fuel prices that home probably has been
insulated and fitted with storm windows so that the
heat loss of the home has been reduced. This
15
Fig. 14: Proper and Improper Locations
of Draft Regulator
Fig. 13: Recommended Smokepipe Arrangement
and Chimney Requirements
3. For the same reasons as in (2.) above, heat
extractors mounted into the breeching are not
recommended.
requires less fuel to be burned and sends less heat
up the chimney.
H. INSTALL ELECTRIC WIRING in accordance with
National Electrical Code and local regulations. A
separate ELECTRICAL CIRCUIT should be run from
meter with a Fused Disconnect Switch in the Circuit.
Wiring should conform to Figures 17 thru 23.
A new boiler probably has a higher efficiency than
the boiler being replaced. That probably means that
the stack temperature from the new boiler will be
lower than that from the old boiler and with less
room air being drawn up the chimney to dilute the
stack gases. The combination of a large uninsulated
chimney, reduced firing rate, reduced firing time,
lower stack temperature and less dilution air can, in
some cases, contribute to the condensing of small
amounts of water vapor in the chimney. Such
condensation, when it occurs, can cause chimney
deterioration. In extreme cases, condensed water
may be visible on the outside of the breeching or
chimney. In those extreme cases, the chimney may
have to be lined to insulate the chimney and thus
prevent the condensation. The addition of dilution
air into the chimney may assist in drying the
chimney interior surfaces.
CANADA- Refer to CSA standard C22.2 Part 1, 1990,
Electrical Features of Fuel Burning Equipment (Gas
and Oil).
I. FUEL UNITS AND OIL LINES
SINGLE-PIPE OIL LINES - Standard burners are
provided with single-stage 3450 rpm fuel units with
the by-pass plug removed for single-pipe installations.
The single-stage fuel unit may be installed single-pipe
with gravity feed or lift. Maximum allowable lift is 8
feet. See Figure 15.
TWO-PIPE OIL LINES - For two-pipe systems where
more lift is required, the two-stage fuel unit is
recommended. Table 4 (single-stage) and Table 5
(two-stage) show allowable lift and lengths of 3/8-inch
and 1/2-inch OD tubing for both suction and return
lines. Refer to Figure 16.
A massive chimney on a cold, or exposed outside
wall may have produced adequate draft when it was
fired with a higher input and greater volumes of
heated gases. With reduced input and volume, the
draft may be severely affected. In one instance our
research showed a new chimney of adequate sizing
produced only -.035" W.C. after 30 minutes of
continuous firing at 13.0% CO2. Outside wall
chimneys take longer to heat up and can have .00"
W.C. draft at burner startup. You may have to
consider a special alloy chimney flue liner with
insulation around it and a stabilizing draft cap or
even a draft inducing fan in severe cases.
Be sure that all oil line connections are absolutely
airtight. Check all connections and joints. Flared
fittings are recommended. Do not use compression
fittings or PTFE ("Teflon®") tape.
Open the air-bleed valve and start the burner. For
clean bleed, slip a 3/16" ID hose over the end of the
bleed valve and bleed into a container. Continue to
bleed for 15 seconds after oil is free of air bubbles.
Stop burner and close valve.
16
TABLE 4: SINGLE-STAGE UNITS (3450 RPM) -
TWO-PIPE SYSTEMS
Manimum Length of Tubing
"H" + "R" (See Figure 16)
Lift "H"
(See Fig. 16)
3/8" OD
1/2" OD
Tubing (3 GPH) Tubing (3 GPH)
0'
1'
84'
78'
73'
68'
63'
57'
52'
47'
42'
36'
31'
26'
21'
---
100'
100'
100'
100'
100'
100'
100'
100'
100'
100'
100'
100'
83'
2'
3'
4'
5'
6'
7'
Figure 15
8'
9'
10'
11'
12'
13'
14'
IMPORTANT
Single-pipe installations must be absolutely
airtight or leaks or loss of prime may result.
Bleed line and fuel unit completely.
62'
---
41'
TABLE 5: TWO-STAGE UNITS (3450 RPM) -
TWO-PIPE SYSTEMS
Maximum Length of Tubing
"H" + "R" (See Figure 16)
Lift "H"
(See Fig. 16)
3/8" OD
1/2" OD
Tubing (3 GPH) Tubing (3 GPH)
0'
2'
93'
85'
77'
69'
60'
52'
44'
36'
27'
---
100'
100'
100'
100'
100'
100'
100'
100'
100'
76'
4'
6'
8'
10'
12'
14'
16'
18'
Figure 16
17
Fig. 17: Wiring Diagram for Steam Boilers with Standard Hydrolevel CG-450 Probe LWCO,
Beckett AFG Burner and Controls, with or without Tankless Heater
Fig. 18: Wiring Diagram for Steam Boilers with Optional McDonnell & Miller PS-801 Probe LWCO,
Beckett AFG Burner and Controls, with or without Tankless Heater
BOILER SEQUENCE OF OPERATION WITH PROBE LWCO
When the thermostat calls for heat, it energizes the cad cell primary control, bringing on the burner. The burner will operate until the
thermostat is satisfied or the limit setting on the high limit is reached. When the high limit control restores the circuit on a drop in
pressure, the burner will start if the thermostat is still calling for heat.
Any of the probe low water cutoffs will shut down the burner after a 10-15 second delay, if the water level in the boiler drops too low.
The Hydrolevel CG-450 and the McDonnell & Miller PS-804-120 low water cutoffs will shut down the burner for 90 seconds every 10
minutes of firing time to allow water level to stabilize. If the water level is too low the burner will not be allowed to restart.
Any of the probe low water cutoffs reset and restart the burner with a call for heat a few seconds after the water is returned to its
normallevel.
On burner start, if the cad cell does not see flame within approximately 45 seconds, primary control will lock out on safety and must be
reset before burner can be restarted.
When there is no demand for heat, the operating control will maintain the boiler water temperature at the selected setting for proper
operation of the domestic water heater, if equipped with optional tankless heater.
18
Fig. 19: Wiring Diagram for Steam Boilers with Optional McDonnell & Miller PS-804-120 Probe LWCO,
Beckett AFG Burner and Controls, with or without Tankless Heater
NOTE: The McDonnell Miller low water cut off incorporates a 10 second delay to prevent nuisance burner cut-off due to rapid
water level fluctuations. The LWCO also has a time delay of 15 seconds which allows additional fill time after water touches the
probe. Red LED indicates a low water condition.
Fig. 20: Wiring Diagram for Steam Boilers with McDonnell & Miller #67 LWCO,
Beckett AFG Burner and Controls, with or without Tankless Heater
BOILER SEQUENCE OF OPERATION WITH FLOAT LWCO
When the thermostat calls for heat, it energizes the cad cell primary control, bringing on the burner. The burner will operate until
the thermostat is satisfied or the limit setting on the high limit is reached. When the high limit control restores the circuit on a
drop in pressure, the burner will start if the thermostat is still calling for heat. The low water cut off will shut down the burner if the
water level in the boiler drops too low. The control resets and restarts the burner with a call for heat a few seconds after the water
is returned to its normal level.
On burner start, if the cad cell does not see flame within approximately 45 seconds, primary control will lock out on safety and
must be reset before burner can be restarted.
When there is no demand for heat, the operating control will maintain the boiler water temperature at the selected setting for
proper operation of the domestic water heater, if equipped with optional tankless heater.
19
Fig. 21: Wiring Diagram for Water Boilers with Beckett AFG Burner and Controls, without Tankless Heater
SEQUENCE OF OPERATION
A call for heat by the thermostat energizes the L8148A control which in turn energizes the R4184D primary control to turn on the
burner. If burner ignites within approximately 45 seconds and the cad cell sees flame, the burner will continue to operate until the call
for heat is satisfied or the setting of the high limit is reached. The circulator will operate as long as the thermostat is calling for heat. If
the thermostat is not satisfied and the high limit is reached, the circulator will continue to operate, and the burner will stop until the high
limit is closed by a drop in boiler water temperature.
Fig. 22: Wiring Diagram for Water Boilers with Beckett AFG Burner and Controls, with Tankless Heater
SEQUENCE OF OPERATION
A call for heat by the thermostat energizes the L8124C control which in turn energizes the R4184D primary control to turn on the
burner. If burner ignites within approximately 45 seconds and the cad cell sees flame the burner will continue to operate until the call
for heat is satisfied. The circulator will also operate when the thermostat calls for heat if the boiler water temperature is up to the setting
of the low limit in the L8124C control. If boiler water temperature is below the low limit setting the burner will operate but the circulator
will not, giving preference to the domestic hot water demand.
On call for heat by the thermostat the burner will continue to operate until the thermostat is satisfied or the setting of the high limit is
reached. If the thermostat is not satisfied when the high limit is reached the burner will stop but the circulator will continue to operate
until the thermostat is satisfied. Any time the boiler water temperature drops below the setting of the low limit the burner will be
energized in order to maintain domestic water temperature.
20
SECTION IV: OPERATING AND SERVICE INSTRUCTIONS
WARNING
All boilers equipped with burner swing door have a potential hazard which can cause severe property
damage, personal injury or loss of life if ignored. Before opening swing door, turn off service switch to
boiler to prevent accidental firing of burner outside the combustion chamber. Be sure to tighten swing door
fastener completely when service is completed.
A. ALWAYS INSPECT INSTALLATION BEFORE
(Note - If make-up water line is equipped with
pressure reducing valve, system will
automatically fill to 12 psi. Leave globe valve
open).
STARTING BURNER.
B. FILL HEATING SYSTEM WITH WATER.
NOTE: It is important, especially in a steam system,
to properly remove the oil and dirt from the system.
Failure to clean the system can result in erratic water
lines and surging.
j. Open isolation valve in boiler supply piping.
k. Remove hose from bib cock.
C. CHECK CONTROLS, WIRING AND BURNER to be
sure that all connections are tight and burner is rigid,
that all electrical connections have been completed and
fuses installed, and that oil tank is filled and oil lines
have been tested.
CLEAN HEATING SYSTEM IF boiler water or
condensate return water is dirty or if erratic water lines
or surging exist after a few days of boiler operation.
Refer to step "N" for proper cleaning instructions for
steam and water boilers.
D. LUBRICATION — Follow instruction on burner and
circulator label to lubricate, if oil lubricated. Most
motors currently used on residential type burners
employ permanently lubricated bearings and thus do
not require any field lubrication. Water lubricated
circulators do not need field lubrication.
1. STEAM BOILERS — Fill boiler to normal water
line. Refer to Figure No. 1C.
2. HOT WATER BOILERS. Fill entire heating system
with water and vent air from system. Use the
following procedure on a series loop or multi-zoned
system installed as per Figure 9, to remove air from
system when filling:
Do not over-lubricate. This can cause as much trouble
as no lubrication at all.
E. SET CONTROLS with burner service switch turned
a. Close isolation valve in boiler supply piping.
“OFF”.
b. Isolate all circuits by closing zone valves or
balancing valves.
1. SET ROOM THERMOSTAT about 10° above
room temperature.
c. Attach a hose to bib cock located just below
isolation valve in boiler supply piping.
2. PRESS RED RESET BUTTON on primary control
(R4184D/R8184G) and release.
(Note - Terminate hose in five gallon bucket at a
suitable floor drain or outdoor area).
3. On STEAM BOILERS, set cut-in pressure on
PA404 pressuretrol for three (3) pounds and
differential pressure for two (2) pounds. These
pressures may be varied to suit individual
requirements of installation.
d. Starting with one circuit, open zone valve.
e. Open bib cock.
f. Open fill valve (make-up water line should be
located directly above isolation valve in boiler
supply piping).
4. On STEAM BOILERS WITH TANKLESS
DOMESTIC WATER HEATERS, set boiler water
temperature dial on L4006 operating control at
190°F (max.). Set differential at 10°.
g. Allow water to overflow from bucket until
discharge from hose is bubble free for 30
seconds.
5. On WATER BOILERS WITHOUT TANKLESS
HEATERS, set high limit dial on L8148 at 210°F.
This temperature may be varied to suit
requirements of installation.
h. Open zone valve to the second zone to be
purged, then close the first. Repeat this step
until all zones have been purged, but always
have one zone open. At completion, open all
zone valves.
6. On WATER BOILERS WITH TANKLESS
HEATERS, set operating control dial (low limit) on
L8124 at 190°F and high limit dial at 210°F.
Operating control (low limit) must be a minimum
of 20° below high limit setting. Set differential at
25°.
i. Close bib cock, continue filling the system until
the pressure gauge reads 12 psi. Close fill valve.
21
NOTICE
Burner-specific references in the following instructions pertain to the Beckett AFG, supplied as
standard equipment. For optional burners, Riello R40 and Carlin EZ-1HP and 102CRD-3, consult
Table 6 at the rear of this manual for specifications, the instruction booklet shipped with the
burner, and the appropriate Supplemental Instructions shipped with the boiler:
Burnham Part Number
Supplemental Instructions for:
Riello R40
8142761
8142759
8142760
Carlin EZ-1HP
Carlin 102CRD-3
V72 thru V77; V713 and V714:
F. REMOVE GUN ASSEMBLY
"L1" and "F" head burners have a fixed head which
is non-adjustable. To check combustion head
location refer to Figure 24.
1. Items to be checked are nozzle size, type, and
angle; head size (and setting on MD(V1)head); gun
setting; and positioning of electrodes. This
informations is shown in Figures 23 and 24 and
Table 6 (at rear of manual).
V78 & V79:
“V1” (variable) head burners have the ability to
control air by moving the head either forward or
back.
2. Reinstall gun assembly.
G. ADJUST OIL BURNER BEFORE STARTING.
Loosen the adjusting plate assembly hold down
screw. Slide the head and plate to the required
firing rate setting as shown in Figure 24. Tighten
the screw and knurled nut.
1. SET BURNER AIR BAND AND AIR SHUTTER,
see Table 6 at rear of manual..
2. OPEN ALL OIL LINE VALVES.
3. Attach a plastic hose to fuel pump vent fitting and
provide a pan to catch the oil.
It might be necessary to move the head forward or
back one position at a time to optimize the smoke
and CO2 readings. See Figure 24.
4. REMOVE GAUGE PORT PLUG from fuel pump
and install pressure gauge capable of reading at
least 150 PSI.
3. ADJUST DRAFT REGULATOR for a draft
of — .02” (water gauge) over the fire after chimney
has reached operating temperature and while
burner is running.
5. OPEN FLAME OBSERVATION DOOR on front
of boiler.
4. READJUST AIR BANDS on burner for a light
orange colored flame while the draft over the fire is
—.02”. Use a smoke tester and adjust air for
minimum smoke (not to exceed #1) with a
minimum of excess air. Make final check using
suitable instrumentation to obtain a CO2 of 11.5 to
12.5% with draft of —.02” (water gauge) in fire
box. These settings will assure a safe and efficient
operating condition. If the flame appears stringy
instead of a solid fire, try another nozzle of the
same type. Flame should be solid and compact.
After all adjustments are made recheck for a draft
of —.02” over the fire.
H. START OIL BURNER.
1. Open vent fitting on fuel pump.
2. TURN ‘ON’ BURNER service switch and allow
burner to run until oil flows from vent fitting in a
SOLID stream without air bubbles for
approximately 10 seconds.
3. Close vent fitting and burner flame should start
immediately.
I. ADJUST OIL PRESSURE.
1. Locate oil pressure adjusting screw and turn screw
to obtain 140 PSI pressure (100 PSI for V74R
only).
2. DO NOT REMOVE PRESSURE GAUGE until
later.
J. OTHER ADJUSTMENTS
1. ADJUST THE AIR BAND AND/OR AIR
SHUTTER.
(Non-Burnham Drawing
Copy from other Manual)
Adjust air supply by loosening lock screws and
moving the air shutter and if necessary the air band.
Refer to Table 6 for preliminary settings.
2. ADJUST THE COMBUSTION HEAD.
Fig. 23: "F" Head Electrode Positioning and Gun
Setting (Beckett AFG)
22
(Non-Burnham Drawing,
Copy from LE Manual, 81433010R4, Page 13, without
"Figure 12A, 12B, 12C and 12D"; sample enclosed)
Fig. 24: "L1" and "V1" Head Electrode Positioning and Gun Setting (Beckett AFG)
5. TURN “OFF” BURNER and remove pressure
gauge. Install gauge port plug and tighten. Start
burner again.
6. CAD CELL LOCATION AND SERVICE
The burner is supplied with a cadmium sulfide
flame detector mounted at the factory, mounted on
the bottom of the ignitor. See Figure 25. To service
cad cell or to replace the plug in portion, swing
open the ignitor. After service is complete, be sure
to fasten down the ignitor.
7. FLAME FAILURE
The V7 boiler controls operate the burner
automatically. If for unknown reasons the burner
ceases to fire and the reset button on the primary
control has tripped, the burner has experienced
ignition failure. Before pressing the reset button
call your serviceman immediately.
Figure 25: Cad Cell Location
23
CAD CELL TEST
g. Open line switch. Clean cell face and see that
cell is securely in socket. Reconnect leads. Reset
safety switch.
h. Close line switch. If burner starts and runs
beyond safety switch cut-out time, cell is good.
If not, install new cell.
K. CHECK FOR CLEAN CUT OFF OF BURNER.
3. WARNING — Check High Limit Control —
Jumper Thermostat Terminals. Allow burner to
operate until shut-down by limit. Installation is not
considered complete until this check has been
made.
1. AIR IN THE OIL LINE between fuel unit and
nozzle will compress when burner is on and will
expand when burner stops, causing oil to squirt
from nozzle at low pressure as burner slows down
and causing nozzle to drip after burner stops.
Usually cycling the burner operation about 5 to 10
times will rid oil line of this air.
REMOVE JUMPER.
4. Check low water cut off control with water level at
normal water line (see Figure 1C). Raise thermostat
setting to allow burner to operate. Open boiler drain
to allow water level to drop to bottom of sight glass
until burner operation is shut-down by low water
cutoff.
2. IF NOZZLE CONTINUES TO DRIP, repeat step
K.1.. If this does not stop the dripping, remove
cutoff valve and seat, and wipe both with a clean
cloth until clean, then replace and readjust oil
pressure. If dripping or after burn persist replace
fuel pump.
Close boiler drain and refill to normal water line.
Burner should automatically restart during fill.
Lower thermostat setting.
L. TEST CONTROLS.
5. Check operating control on boiler equipped with
tankless heaters. With burner off, draw hot water
until burner starts, then turn off hot water and
check burner shut-down.
WARNING
Before installation of the boiler is considered
complete, the operation of the boiler controls
should be checked, particularly the primary
control and high limit control.
IF CONTROLS DO NOT MEET REQUIREMENTS
OUTLINED IN PARAGRAPH L., REPLACE
CONTROL AND REPEAT CHECK-OUT
PROCEDURES.
1. Check thermostat operation. Raise and lower
thermostat setting as required to start and stop
burner.
M. MAINTENANCE OF LOW WATER CUTOFF
DEVICES
2. VERIFY PRIMARY CONTROL SAFETY
FEATURES using procedures outlined in
Instructions furnished with control (See back of
control cover) or instructions as follows:
IMPORTANT
Probe and float type low water cut-off devices
require annual inspection and maintenance.
CHECKOUT PROCEDURE
1. PROBE TYPE LOW WATER CUT-OFF
FOR SERVICEMAN ONLY
Although these devices are solid state in their
operation, the probe is exposed to possible
contamination in the boiler water and subject to
fouling.
a. Check wiring connections. Close line switch.
Check power at control.
PRIMARY RELAY TEST
It is important to physically remove the probe from
the boiler tapping annually and inspect that probe
for accumulation of scale or sediment.
b. Disconnect cad cell leads (f-f). Reset safety
switch.
c. Set controller to call for heat. Burner should
start.
Follow these steps to inspect, clean and/or replace
the probe:
d. Jumper F-F terminal within 15 to 30 seconds.
Burner should run.
a. Turn off electric service to the boiler.
b. Drain boiler water to a level below the tapping
for the probe.
e. Remove F-F Jumper. Burner shuts down in
approximately 15 to 60 seconds.
c. Disconnect wiring connections between the low
water cutoff control and the probe.
f. If burner operates as described, relay is good. If
not, install new relay.
24
d. Dismount the low water cutoff control from the
probe.
required. Examine all visible wiring for brittle or
worn insulation and make sure electrical contacts
are clean and that they function properly. Give
special attention to solder joints on bellows and
float when this type of control is used. Check float
for evidence of collapse and check mercury bulb
(where applicable) for mercury separation or
discoloration. Do not attempt to repair mechanisms
in the field. Complete replacement mechanisms,
including necessary gaskets and installation
instructions are available from the manufacturer.
e. Unscrew the probe from the boiler tapping.
f. Inspect that portion of the probe that is exposed
to the boiler water for a scale or sediment
buildup.
g. Light deposits may be removed by wiping the
probe with a damp cloth. Wiping the probe with
a cloth soaked in vinegar will remove more
tenacious lime deposits. The most stubborn
deposits may be removed from the probe by
using a diluted amount, 3 parts of water to 1
part of phosphoric acid (H2PO4).
N. BOILER AND SYSTEM CLEANING
INSTRUCTIONS FOR TROUBLE FREE
OPERATION.
1. STEAM BOILERS
CAUTION
a. Oil, greases & sediments which accumulate in a
new boiler and piping must be removed from the
system in order to prevent an unsteady water
line and carry over of the water into the supply
main above boiler.
Exercise caution when handling phosphoric acid
and follow the instruction label on its container.
h. Clean the pipe threads of the probe to remove
old, hardened pipe dope and other foreign
matter.
Operate the boiler with steam in the entire
system for a few days allowing the condensate to
return to the boiler. If the condensate can
temporarily be wasted, operate boiler only for
the length of time it takes for condensate to run
clear. If the latter cannot be achieved or if the
condensate is returned to the boiler, boil out the
boiler using the SURFACE BLOWOFF
connection, see Figure 4.
i. Apply a moderate amount of good quality pipe
dope to the pipe threads on the probe, leaving
the two end threads bare. Do not use PTFE
(Teflon) tape.
j. Screw the probe into the boiler tapping.
k. Mount the low water cutoff control on the probe.
l. Reconnect the control to probe wiring.
m. Fill the boiler to its normal waterline.
i. Drain boiler until 1” of water is visible in
gauge glass. Run temporary 1½” pipe line
from the surface blowoff connection to an
open drain or some other location where hot
water may be discharged safely. Do not
install valve in this line.
n. Add boiler water treatment compound as needed
(refer to paragraph N.).
o. Restore electric service to the boiler.
p. Fire burner to bring the water in the boiler to a
boil to drive off free oxygen.
ii. Drain about 5 gallons of hot water from
boiler into a container and dissolve into it
an appropriate amount of recommended
boil out compound. Remove safety valve &
add solution to boiler water thru exposed
tapping using a funnel.
q. WARNING — BEFORE RETURNING
BOILER TO SERVICE: Follow the low water
cutoff check out procedure in step L.4..
2. FLOAT TYPE LOW WATER CUT-OFF
During the heating season, if an external low water
cutoff is on the boiler, the blow off valve should be
opened once a month (use greater frequency where
conditions warrant), to flush out the sediment
chamber so the device will be free to function
properly.
NOTICE
Check with local authorities or consult local
water treatment services for acceptable chemical
cleaning compounds.
Low-water cutoffs and water feeders should be
dismantled annually by qualified personnel, to the
extent necessary to insure freedom from
obstructions and proper functioning of the working
parts. Inspect connecting lines to boiler for
accumulation of mud, scale, etc., and clean as
iii. Start burner and operate sufficiently to boil
the water without producing steam pressure.
Boil for about 5 hours. Open boiler feed
pipe sufficiently to permit a steady trickle of
water from the surface blowoff pipe.
25
Continue this slow boiling and trickle of
overflow for several hours until the water
coming from the overflow is clear.
v. When boiler has cooled down sufficiently
(crown sheet of sections are not too hot to
touch), close the drain cocks at boiler and in
return main and feed water slowly up to
normal level in boiler. Turn on oil burner
and allow boiler to steam for 10 minutes,
then turn off burner. Draw off one quart of
water from bottom gauge glass fitting and
discard. Draw off another quart sample and
if this sample is not clear, repeat the cycle
of draining the boiler and return main and
refilling the boiler until sample is clear.
iv. Stop burner and drain boiler in a manner
and to a location that hot water can be
discharged with safety.
v. Refill boiler to normal water line. If water
in gauge glass does not appear to be clear,
repeat steps (i. thru iii.) and boil out the
boiler for a longer time.
b. Low pressure steam boilers such as the V7
Series should be maintained with appropriate
water treatment compounds. Add suitable water
treatment compounds as recommended by your
qualified water treatment company.
vi. If the boiler water becomes dirty again at a
later date due to additional sediment
loosened up in the piping, close gate valve
in Hartford Loop, open drain cock in return
main, turn on oil burner and allow
c. Remove temporary surface blowoff piping, plug
tapping and reinstall safety valve. Boil or bring
water temperature to 180°F promptly in order to
drive off the dissolved gases in the fresh water.
Condensate to flow to drain until it has run
clear for at least 30 minutes while feeding
water to boiler so as to maintain normal
water level. Turn off oil burner, drain
boiler, open gate valve in Hartford Loop,
then repeat step 1 above.
d. If unsteady water line, foaming or priming
persist, install gate valve in Hartford Loop and
drain valves in return main and at boiler as
shown in Figure 8 and proceed as follows:
e. Make pH or Alkalinity Test.
i
Connect hoses from drain cocks to floor
drain. Close gate valve in Hartford Loop
and open drain cock in return main. Fill
boiler to normal water level, turn on oil
burner and operate boiler at this water level
for at least 30 minutes after the condensate
begins to run hot, then turn off burner.
After boiler and system have been cleaned and
refilled as previously described, test the pH of
the water in the system. This can easily be done
by drawing a small sample of boiler water and
testing with hydrion paper which is used in the
same manner as litmus paper, except it gives
specific readings. A color chart on the side of
the small hydrion dispenser gives the reading in
pH. Hydrion paper is inexpensive and
obtainable from any chemical supply house or
through your local druggist. The pH should be
higher than 7, but lower than 11. Add some of
the washout chemical (caustic soda), if
Close all radiator valves. Remove all supply
main air valves and plug the openings in
supply main.
ii. Draw about 5 gallons of hot water from
boiler into a container and dissolve into it
the appropriate amount of a recommended
boilout compound. Remove safety valve
from boiler and pour this solution into
boiler, then reinstall safety valve.
necessary, to bring the pH within the specified
range.
f. Boiler is now ready to be put into service.
2. WATER BOILERS
iii. Turn on oil burner and keep operating
while feeding water to boiler slowly. This
will raise water level in boiler slowly so that
water will be boiling hot and will rise
slowly into supply main and back through
return main, flowing from drain hose at
about 180°F. Continue until water runs
clear from drain hose for at least 30
minutes.
a. Filling of Boiler and System — General —-In a
hot water heating system, the boiler and entire
system (other than the expansion tank) must be
full of water for satisfactory operation. Water
should be added to the system until the boiler
pressure gauge registers 12 psi. To insure that
the system is full, water should come out of all
air vents when opened.
iv. Stop feeding water to boiler but continue
operating oil burner until excess water in
boiler flows out through supply main and
water lowers (by steaming) until it reaches
normal level in boiler. Turn off oil burner.
Drain boiler. Open all radiator valves.
Reinstall all supply main air valves. Open
gate valve in Hartford Loop.
b. Boiling Out of Boiler and System. The oil and
grease which accumulate in a new hot water
boiler can be washed out in the following
manner.
i. Remove safety relief valve using extreme
care to avoid damaging it.
ii. Add an appropriate amount of
26
recommended boil out compound.
iii. Replace safety relief valve.
iv. Fill the entire system with water.
v. Start firing the boiler.
and can vary from sample to sample. For all of
those reasons a spare nozzle is a desirable item for
a serviceman to have.
2. FLAME SHAPE — Looking into the combustion
chamber through the observation door, the flame
should appear straight with no sparklers rolling up
toward the crown of the chamber. If the flame drags
to the right or left, sends sparklers upward or makes
wet spots on the target wall, the nozzle should be
replaced. If the condition persists look for fuel
leaks, air leaks, water or dirt in the fuel as
described above.
vi. Circulate the water through the entire
system.
vii. Vent the system, including the radiation.
viii. Allow boiler water to reach operating
temperature, if possible.
ix. Continue to circulate the water for a few
hours.
3. FUEL LEAKS — Any fuel leak between the pump
and the nozzle will be detrimental to good
combustion results. Look for wet surfaces in the air
tube, under the ignitor, and around the air inlet.
Any such leaks should be repaired as they may
cause erratic burning of the fuel and in the extreme
case may become a fire hazard.
x. Stop firing the boiler.
xi. Drain the system in a manner and to a
location that hot water can be discharged
with safety.
xii. Remove plugs from all available returns and
wash the water side of the boiler as
thoroughly as possible, using a high-
pressure water stream.
4. AIR LEAKS — Any such leaks should be repaired,
as they may cause erratic burning of the fuel and in
extreme cases may become a fire hazard.
xiii. Refill the system with fresh water.
c. Add appropriate boiler water treatment
compounds as recommended by your qualified
water treatment company.
5. GASKET LEAKS — If 11.5 to 12.5% CO2 with a
#1 smoke cannot be obtained in the breeching, look
for air leaks around the burner mounting gasket,
observation door, and canopy gasket. Such air leaks
will cause a lower CO2 reading in the breeching.
The smaller the firing rate the greater effect an air
leak can have on CO2 readings.
d. Make pH or Alkalinity Test.
After boiler and system have been cleaned and
refilled as previously described, test the pH of
the water in the system. This can easily be done
by drawing a small sample of boiler water and
testing with hydrion paper which is used in the
same manner as litmus paper, except it gives
specific readings. A color chart on the side of
the small hydrion dispenser gives the reading
pH. Hydrion paper is inexpensive and
obtainable from any chemical supply house or
thru your local druggist. The pH should be
higher than 7 but lower than 11. Add
appropriate water treatment chemicals, if
necessary, to bring the pH within the specified
range. With this lower level of protection, care
must be exercised to eliminate all of the free
oxygen in the system.
6. DIRT — A fuel filter is a good investment.
Accidental accumulation of dirt in the fuel system
can clog the nozzle or nozzle strainer and produce a
poor spray pattern from the nozzle. The smaller the
firing rate, the smaller the slots become in the
nozzle and the more prone to plugging it becomes
with the same amount of dirt.
7. WATER — Water in the fuel in large amounts will
stall the fuel pump. Water in the fuel in smaller
amounts will cause excessive wear on the pump, but
more importantly water doesn’t burn. It chills the
flame and causes smoke and unburned fuel to pass
out of the combustion chamber and clog the
flueways of the boiler.
e. Boiler is now ready to be put into service.
8. COLD OIL — If the oil temperature approaching
the fuel pump is 40°F or lower poor combustion or
delayed ignition may result. Cold oil is harder to
atomize at the nozzle. Thus, the spray droplets get
larger and the flame shape gets longer. An outside
fuel tank that is above grade or has fuel lines in a
shallow bury is a good candidate for cold oil. The
best solution is to bury the tank and lines deep
enough to keep the oil above 40°F.
O. HINTS ON COMBUSTION
1. NOZZLES — Although the nozzle is a relatively
inexpensive device, its function is critical to the
successful operation of the oil burner. The selection
of the nozzle supplied with the V7 boiler is the
result of extensive testing to obtain the best flame
shape and efficient combustion. Other brands of the
same spray angle and spray pattern may be used but
may not perform at the expected level of CO2 and
smoke. Nozzles are delicate and should be protected
from dirt and abuse. Nozzles are mass-produced
9. HIGH ALTITUDE INSTALLATIONS
Air openings must be increased at higher altitudes.
Use instruments and set for 11.5 to 12.5% CO2.
27
clean water to prescribed water level.
IMPORTANT
4. Always keep the manual fuel supply valve shut off
if the burner is shut down for an extended period of
time.
SUCTION LINE LEAKS - THE OIL MUST BE
FREE OF AIR. Try bleeding the pump
through a clear tube. There must be no froth
visible. There are various test kits available
to enable you to look at the oil through clear
tubing adapted to the supply line at the
pump fitting. Air eliminators are on the
market that have potential. Also, electronic
sight glasses are being used with good
success. At times, new tubing must be run
to the tank or new fittings put on. Just make
sure you get the air out.
5. To recondition the heating system in the fall season
after a prolonged shut down, follow the instructions
outlined in Section IV, Items A through M.
CAUTION
This boiler contains controls which may
cause the boiler to shut down and not
restart without service. If damage due to
frozen pipes is a possibility, the heating
system should not be left unattended in
cold weather; or appropriate safeguards
and alarms should be installed on the
heating system to prevent damage if the
boiler is inoperative.
Any air leaks in the fuel line will cause an
unstable flame and may cause delayed
ignition noises. Use only flare fittings in the
fuel lines.
10. START-UP NOISE — Late ignition is the cause of
start-up noises. If it occurs recheck for electrode
settings, flame shape, air or water in the fuel lines.
11. SHUT DOWN NOISE — If the flame runs out of
air before it runs out of fuel, an after burn with
noise may occur. That may be the result of a faulty
cut-off valve in the fuel pump, or it may be air
trapped in the nozzle line. It may take several firing
cycles for that air to be fully vented through the
nozzle. Water in the fuel or poor flame shape can
also cause shut down noises.
Q. FREQUENT WATER ADDITION
IMPORTANT
CHECK TEST PROCEDURE. A very good test for
isolating fuel side problems is to disconnect the
fuel system and with a 24" length of tubing, fire
out of an auxiliary five gallon pail of clean, fresh,
warm #2 oil from another source. If the burner
runs successfully when drawing out of the
auxiliary pail then the problem is isolated to the
fuel or fuel lines being used on the jobsite.
A leaky system will increase the volume of make-up
water supplied to the boiler which can significantly
shorten the life of the boiler. Entrained in make-up
water are dissolved minerals and oxygen. When the
fresh, cool make-up water is heated in the boiler the
minerals fall out as sediment and the oxygen
P. ATTENTION TO BOILER WHILE NOT IN
OPERATION.
escapes as a gas. Both can result in reduced boiler
life. The accumulation of sediment can eventually
isolate the water from contacting the cast iron.
When this happens the cast iron in that area gets
extremely hot and eventually cracks. The presence
of free oxygen in the boiler creates a corrosive
atmosphere which, if the concentration becomes
high enough, can corrode the cast iron through
from the inside. Since neither of these failure types
are the result of a casting defect the warranty does
not apply. Clearly it is in everyone’s best interest to
prevent this type of failure. The maintenance of
system integrity is the best method to achieve this.
1. IMPORTANT
IF BOILER IS NOT USED DURING WINTER
TIME, IT MUST BE FULLY DRAINED TO
PREVENT FREEZE DAMAGE.
2. Spray inside surfaces with light lubricating or
crankcase oil using gun with extended stem so as to
reach all corners.
3. With steam boilers, at end of season add sufficient
water to fill boiler to top of water column and leave
it that way until fall when water should be drained
again to proper level. If at this time boiler water is
dirty, drain water, flush out boiler, and refill with
28
(Non-Burnham Drawing
Copy from other Manual)
AQUASTAT SWITCHING ACTION WITHIN L8124C
CONTROL
The switching action within the L8124C control has
EXAMPLE: Set point of 140°F; differential set at 25°F.
On a temperature rise, R-B will break and R-W will make
at 155°F. On a temperature fall, R-B will make and R-W
will break at 130°F.
three settings:
1. high limit
2. low limit
3. adjustable differential
Set low limit indicator at the minimum temperature
recommended for domestic hot water supply. This setting
must be at least 20°F below high limit setting to prevent
one switch from locking out the other.
HIGH LIMIT OPERATION —-
The high limit opens and turns off the burner when the
water temperature reaches the set point. The high limit
automatically resets after the water temperature drops past
the set point and through the 10°F differential.
Set the indicator at desired shutoff temperature.
Set the differential the desired number of degrees.
25°F differential gives longest burner cycles.
AQUASTAT SWITCHING ACTION WITHIN L8148A
CONTROLS
LOW LIMIT OPERATION —-
On a temperature rise, with the adjustable differential
at the minimum setting of 10°F, the burner circuit (R-B)
breaks and the circulator circuit (R-W) makes at the low
limit set point. On a temperature drop of 10°F below the set
point, the R-B circuit makes and the R-W circuit breaks.
The switching action in the L8148A control has one
setting, the high limit. The switching relay is controlled by
the low voltage room thermostat. On a call for heat, the
relay contacts make to complete the line voltage circulator
circuit and also the burner circuit if the boiler water
temperature is below the high limit setting. The high limit
switch shuts off the burner if boiler water temperature
exceeds the high limit setting.
ADJUSTABLE DIFFERENTIAL —-
At any differential setting greater than 10°F, the R-B
make temperature and R-W break temperature will remain
the same-control setting minus 10°F. The R-B break and R-
W make temperature will be the set point temperature plus
the difference between the differential setting and 10°F.
Set the indicator at the desired shutoff temperature.
SECTION V: BOILER CLEANING
WARNING
All boiler cleaning must be completed with burner service switch turned off. Boilers
equipped with burner swing door have a potential hazard which can cause severe property
damage, personal injury or loss of life if ignored. Before opening swing door, turn off
service switch to boiler to prevent accidental firing of burner outside the combustion
chamber. Be sure to tighten swing door fastener completely when service is completed.
29
smokepipe, burner mounting plate, burner swing door
and all flue plates are secured in place.
A. CLEAN THE FLUEWAYS (See Figure 26).
1. Prior to cleaning boiler, lay a protective cloth or
plastic over combustion chamber blanket to collect
debris falling from flueways.
1. Install the canopy taking care to align the gaskets
without blocking the flueways. If gasket is
damaged, replace as needed.
2. For access to firebox
2. Reinstall flue plates, making sure gasket on each
plate is in place and forms gas tight seal. If
damaged replace as needed.
On boilers with burner swing door and flexible fuel
line(s), remove fastener securing door and swing
door open. For full access to firebox, remove burner
and swing door from mounting plate by pulling
hairpin cotter from bottom of hinge pin and
removing pin from hinge. Set burner aside. Remove
swing door mounting plate, see Figure 6.
3. Reinstall jacket top panel and secure with sheet
metal screws. Replace jacket upper right side access
panel.
4. Reinstall smokepipe on canopy and secure to collar
with sheet metal screws.
5. Install swing door mounting plate to front section
with fasteners, see Figure 6.
6. Reinstall burner in reverse order of disassembly
outlined in paragraph A.2 above. For details, see
Figure 6.
3. For cleaning from the side:
a. Lift the jacket's upper right side access panel off
to expose the flue cleanout plates.
b. Loosen nuts securing the flue cleanout plates
and remove the plates. The insulation should be
removed with the plates taking care not to
damage the insulation.
4. For cleaning from the top:
a. Lift the jacket's upper right side access panel off
to allow removal of the jacket top panel.
b. Remove as much smokepipe as necessary to
allow removal of the jacket top panel and
canopy (smokebox).
c. Remove the jacket top panel.
d. Remove the canopy, being careful not to damage
the ceramic fiber gasket.
5. Using a 1¼” diameter wire or fibre bristle brush
(30” handle) clean the flueways. Brush from the top
and/or side using horizontal and diagonal strokes
for best results. DO NOT allow brush to strike the
target wall or liner in the chamber.
B. CLEAN TOP OF BOILER SECTIONS (if cleaning
from the top).
Figure 26: Cleaning of Boiler Flueways
Brush and vacuum the tops of the boiler sections.
C. CLEAN THE FIREBOX.
WARNING
Using wire or fibre bristle brush, clean crown of boiler
and inside of water legs. DO NOT allow brush to strike
target wall or blanket in the combustion chamber.
The boiler must be connected to an approved
chimney in good condition. Serious property damage
could result if the boiler is connected to a dirty or
inadequate chimney. The interior of the chimney flue
must be inspected and cleaned before the start of the
heating season and should be inspected periodically
throughout the heating season for any obstructions.
A clean and unobstructed chimney flue is necessary
to allow noxious fumes that could cause injury or loss
of life to vent safely and will contribute toward
maintaining the boiler's efficiency.
D. AFTER CLEANING, remove protective cloth with
debris and vacuum as necessary, but be careful not to
damage blanket. Inspect target wall, combustion
chamber blanket, burner mounting plate insulation and
burner swing door insulation for signs of damage. If
damaged, replace as needed.
E. REASSEMBLE BOILER.
CAUTION: Do not start the burner unless canopy,
30
SECTION VI: REPAIR PARTS
All V7 Series Repair Parts may be obtained through your local Burnham Wholesale distributor. Should you require assistance
in locating a Burnham Distributor in your area, or have questions regarding the availability of Burnham products or repair
parts, please contact your Burnham Regional Sales Office as listed below.
Burnham Corporation Regional Offices
A. Burnham Corporation - Central & Western Regions
P.O. Box 3079
C. Burnham Corporation - Metropolitan Region
P.O. Box 3079
Lancaster, PA 17604-3079
Phone: (717) 481-8400
Lancaster, PA 17604-3079
Phone: (717) 481-8400
FAX: (717) 481-8408
FAX: (717) 481-8409
B. Burnham Sales Corporation - Northeast Region
19-27 Mystic Avenue
D. Burnham Corporation - Mid-Atlantic Region
P.O. Box 3079
Somerville, MA 02145
Lancaster, PA 17604-3079
Phone: (717) 481-8400
Phone: (617) 625-9735
FAX: (617) 625-9736
FAX: (717) 481-8409
Contact Regional Office Indicated for your State
Alabama
Alaska
A
A
A
A
A
A
B
D
A
A
A
A
A
A
A
A
A
A
B
D
B
A
A
A
A
A
Nebraska
A
A
B
Oregon
A
D
B
A
A
A
A
A
B
Nevada
Pennsylvania
Rhode Island
South Carolina
South Dakota
Tennessee
Texas
Arizona
New Hampshire
New Jersey
Arkansas
California
Colorado
Connecticut
Delaware
Florida
Atlantic, Burlington, Camden,
Cape May, Cumberland,
Gloucester, Mercer,
Monmouth, Ocean, Salem
Counties
D
Utah
Vermont
Georgia
Hawaii
All other Counties
C
A
Virginia
New Mexico
New York
Albany, Fulton, Montgomery,
Arlington,Accomack,Clarke,
Idaho
Fairfax,Frederick,Fauquier,
Loudoun,Northampton and
Prince William Counties
All other Counties
D
Illinois
Indiana
Rensselaer, Saratoga,
Schenectady, Schoharie,
Warren, Washington Counties
All Other Counties
B
Iowa
A
A
D
D
A
A
Kansas
Washington
Kentucky
Louisiana
Maine
C
A
A
Washington, D.C.
West Virginia
Wisconsin
North Carolina
North Dakota
Ohio
Maryland
Massachusetts
Michigan
Minnesota
Mississippi
Missouri
Montana
Wyoming
Athens, Belmont, Gallia,
Jefferson, Lawrence, Meigs,
Monroe, and Washington
Counties
D
All other Counties
A
A
Oklahoma
Canada
A
31
BARE BOILER ASSEMBLY
Item
No.
Description
Part No. V72 V713 V73 V714 V74 V75 V76 V77 V78 V79
BARE BOILER ASSEMBLY (See Page 32 for Illustration)
Front Section (Non-Htr.), Machined Water 71727019
Front Section (Non-Htr.), Machined Water 71727015
Front Section (Non-Htr.), Machined Steam 71727018
1
---
1
1
---
1
---
1
1
---
1
1
---
1
1
---
1
1
---
1
1
---
1
1
---
1
1
---
---
1A
2
---
---
Front Section w/Htr. Opening, Machined
Water
71727016
---
---
---
---
1
1
---
---
1
1
1
1
1
1
1
1
1
1
1
1
Front Section w/Htr. Opening, Machined
Steam
2A
3
71727017
Center Section
Center Section
7172202
---
---
---
1
---
1
---
1
2
---
1
---
2
---
3
---
4
---
5
---
6
---
7
71727021
4
Narrow Back Section (Non-Htr.), Machined 7172204
---
---
---
---
---
---
---
Wide Back Section (Non-Htr.), Machined
Water
4A
71727033
1
---
---
1
1
---
---
1
1
1
1
1
1
1
1
1
1
1
1
Wide Back Section (Non-Htr.), Machined
Steam
4B
5
71727034
---
Rear Section w/Htr. Opening, Machined
Rear Section w/Htr. Opening, Machined
5" Cast Iron Slip Nipple
7172203
71727036
7066003
7066001
8202701
82027023
82022033
82027031
82022043
---
---
1
1
---
---
4
---
1
1
---
1
---
1
---
1
---
1
---
1
---
1
---
---
6
6
7
8
2
3
4
5
6
7
8
2½" Cast Iron Slip Nipple
1
2
3
4
5
6
7
8
Rear Target Wall Insulation
1
1
1
1
1
1
1
1
1
1
Combustion Chamber Liner, ½" x 23" x 4"
Combustion Chamber Liner, ½" x 24" x 5"
Combustion Chamber Liner, ½" x 23" x 8"
Combustion Chamber Liner, ½" x 24" x 9"
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
2
---
---
---
---
---
---
---
---
---
2
---
---
---
---
---
---
---
---
2
Combustion Chamber Liner, ½" x 23" x 12" 82027041
Combustion Chamber Liner, ½" x 23" x 16" 82027051
Combustion Chamber Liner, ½" x 23" x 20" 82027061
Combustion Chamber Liner, ½" x 23" x 24" 82027071
Combustion Chamber Liner, ½" x 23" x 28" 82027081
Combustion Chamber Liner, ½" x 23" x 32" 82027091
---
---
---
---
---
---
---
---
2
8A
---
---
---
---
---
---
---
2
---
---
---
---
---
---
---
2
---
---
---
---
---
---
---
2
---
---
---
---
---
---
---
2
---
---
---
---
---
---
---
2
Tie Rod, 3/8"-16 x 7¾" Lg.
Tie Rod, 3/8"-16 x 12½" Lg.
Tie Rod, 3/8"-16 x 17" Lg.
Tie Rod, 3/8"-16 x 20¾" Lg.
Tie Rod, 3/8"-16 x 25¼" Lg.
Tie Rod, 3/8"-16 x 27½" Lg.
Tie Rod, 3/8"-16 x 31½" Lg.
Tie Rod, 3/8"-16 x 36½" Lg.
80861072
80861010
80861011
80861012
80861013
80861014
80861015
80861036
---
---
---
---
---
---
---
2
---
---
---
---
---
---
---
---
---
----
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
9
---
---
---
---
---
---
---
---
---
---
CONTINUED ON PAGES 34 AND 35
33
BARE BOILER ASSEMBLY (CONTINUED)
CONTINUED FROM PAGE 33
Item
No.
Description
Part No. V72 V713 V73 V714 V74 V75 V76 V77 V78 V79
BARE BOILER ASSEMBLY (See Page 34 for Illustration)
10
11
Flue Cover Plate Assembly
6112214
8036068
8036058
7036002
1
2
---
1
2
1
1
1
3
---
1
3
1
1
1
4
1
1
1
5
1
1
1
6
1
1
1
7
1
1
1
8
1
1
1
Heater Cover Plate Gasket - Front Heater
---
---
---
11A Heater Cover Plate Gasket - Rear Heater
12
Blank Heater Cover Plate (WB) - Front Heater
---
---
Tapped Heater Cover Plate (WBTL) - Front
Heater
12A
7036001
7036020
---
---
---
---
1
1
---
---
1
1
1
1
1
1
1
1
1
1
1
1
1
Blank Heater Cover Plate (SB & WB) - Rear
Heater
12B
12C
Tapped Heater Cover Plate (WBTL) - Rear
Heater
7036021
6036036
6031204
6036031
---
---
---
---
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
---
---
222A Heater Carton Assy. - (WBT) Front Heater
---OR---
A54 Heater Carton Assy. - (WBT) Front Heater
13
---
1
---
1
---
1
---
1
---
1
---
---
V1-2 Heater Assy. - (SBT & WBT) - Rear
Heater
13A
1
13B V1-1 Heater Carton Assy. - (WBT) Rear Heater
14 Burner Swing Door Mounting Plate
14A Burner Swing Door Mounting Plate Insulation
6036030
7172705
82027021
72027014
7172706
82027022
72027015
7022701
80861614
80861667
7026001
8026015
7202710
611270211
---
1
1
1
1
1
1
2
1
1
1
1
1
1
---
1
---
1
1
1
---
1
---
1
---
1
---
1
---
1
---
1
1
1
1
1
1
1
1
1
1
15
16
Rope Gasket - Burner Mounting Plate - 53" Lg.
Burner Swing Door
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
16A Burner Swing Door Insulation
16B Rope Gasket (Burner Swing Door) - 28" Lg.
16C Hinge
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
16D Hinge Pin
1
1
1
1
1
1
1
1
1
16E Hairpin Cotter
1
1
1
1
1
1
1
1
1
17
18
19
Observation Port Cover
1
1
1
1
1
1
1
1
1
Spring 3/8" I.D. x ½" Lg.
1
1
1
1
1
1
1
1
1
Canopy Sealing Strip (½" x 1" x 98")
V72 Canopy Assembly, Type II
V713 Canopy Assembly
1
1
1
1
1
1
1
1
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
1
611270313 ---
611270311 ---
611270413 ---
611270411 ---
611270511 ---
611270611 ---
611270711 ---
611270811 ---
611270911 ---
20
V73 Canopy Assembly, Type II
V714 Canopy Assembly
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
V74 Canopy Assembly, Type II
V75 Canopy Assembly, Type II
V76 Canopy Assembly, Type II
V77 Canopy Assembly, Type II
V78 Canopy Assembly, Type II
V79 Canopy Assembly, Type II
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
35
TS-39-112-D
V713 and V714 FLUSH JACKET
Item No. Description
Part No.
V713
V714
V713 and V714 Flush Jacket Components - Items 1 thru 6 Include Insulation As Part of Assembly
1
2
Jacket Front Panel Assembly
Jacket Rear Panel Assembly
60427097
60427096
604270314
604270414
604270322
604270422
604270337
604270437
604270336
604270436
604270335
604270435
7042715
1
1
1
1
1
---
1
3
4
5
Jacket Left Side/Top Panel Assembly
Jacket Top Panel Assembly
---
1
---
1
---
1
---
1
Jacket Lower Right Side Panel Assembly
---
1
---
1
Jacket Upper Right Side Access Panel Assembly without Heater Opening (WB
Only)
---
1
6
7
---
1
Jacket Upper Right Side Access Panel Assembly with Heater Opening (WBT Only)
---
Jacket Bracket (WB Only)
Jacket Bracket (WBT Only)
1
1
7042714
37
TS-39-109-D
V72 Thru V79 FLUSH JACKET
Item
No.
Description
Part No.
V72
V73
V74 V75 V76 V77 V78 V79
V72 Thru V79 Flush Jacket Components - Items 1 thru 7 Include Insulation As Part of Ass'y
Jacket Front Panel Ass'y w/o Htr. Opg. (Wtr. Blr.)
Jacket Front Panel Ass'y w/o Htr. Opg. (Stm. Blr.)
Jacket Front Panel Ass'y w/Htr. Opg. (Wtr. Blr.)
Jacket Front Panel Ass'y w/Htr. Opg. (Stm. Blr.)
Plastic Collar Extension-Jkt. Frt. Panel w/Htr. Opg.
Jacket Rear Panel Assembly
60427090
60427091
1
---
---
---
---
1
1
1
1
1
1
1
1
1
60427092
60427094
2
3
8032704
1
1
1
1
1
1
60427093
1
1
1
1
1
1
1
604270241
604270341
604270441
604270541
604270641
604270741
604270841
604270941
604270221
604270321
604270421
604270521
604270621
604270721
604270821
604270921
604270234
604270334
604270434
604270534
604270634
604270734
604270834
604270934
604270233
604270333
604270433
604270533
604270633
604270733
604270833
604270933
604270332
604270432
604270532
604270632
604270732
604270832
604270932
1
---
1
---
---
1
---
---
---
1
---
---
---
---
1
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
4
5
6
Jacket Left Side/Top Panel Assembly
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
Jacket Top Panel Assembly
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
Jacket Lower Right Side Panel Assembly
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
1
---
---
---
---
---
---
1
Jacket Upper Right Side Access Panel Assembly
without Heater Opening
---
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
1
7
---
---
---
---
---
---
1
---
---
---
---
---
---
1
---
---
---
---
---
---
---
---
---
---
---
Jacket Upper Right Side Access Panel Assembly
with Heater Opening
---
---
---
---
---
---
---
---
---
---
39
V73 Thru V79 STEAM BOILERS - TRIM AND CONTROLS
Item
No.
Description
Part No.
V73 V74 V75 V76 V77 V78 V79
V73 Thru V79 STEAM BOILERS - TRIM AND CONTROLS (See Page 40 for Illustration)
1. Draft Regulator
1A
1B
DR-6 Draft Regulator
DR-7 Draft Regulator
8116029
8116001
1
1
1
1
---
1
---
1
---
1
---
---
---
---
2. Instruction Envelope Containing:
2A
2B
2C
Installation and Operating Instructions
10 Year Limited Warranty Mailer (Steam Boilers)
I=B=R Pamphlet
8142711
81460121
81460061
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3. Probe Low Water Cutoff
Low Water Cutoff, Hydrolevel CG450 (less probe)
80160628
80160624
3A
Low Water Cutoff, McDonnell & Miller PS-801-120
1
1
1
1
1
1
1
Low Water Cutoff, McDonnell & Miller PS-804-120
Probe, Hydrolevel EL-1214 (Hydrolevel CG450)
Limit, Honeywell PA404A1009
80160662
80160629
80160300
806603030
806600508
806601520
806600003
8056091
3B
3C
3D
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Syphon, ¼ NPT x 4" x 180°
3D1 Bushing, ¾ NPT x ¼ NPT
3D2 Elbow, ¾ NPT
3D3 Nipple, ¾ NPT x 2"
3E
Gage Glass Set, 6", ConBraCo 20-104-10
4. Float Low Water Cutoff
4A
4B
4C
4D
Low Water Cutoff, McDonnell & Miller 67
80160597
80160300
806603030
8056091
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Limit, Honeywell PA404A1009
Syphon, ¼ NPT x 4" x 180°
Gage Glass Set, 6", ConBraCo 20-104-10
5. Miscellaneous Trim and Controls
5A
5B
Oil Primary Control, Honeywell R8184G1286
80160416
81660530
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Safety Valve, ¾ NPT, 15 psi, ConBraCo 13-511-
08
5B1 Coupling, ¾ NPT
806602561
806600221
806603011
806600507
80160400
80160426
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5B2 Nipple, ¾ NPT x 8"
5C
Drain Valve, ¾ NPT, ConBraCo 31-606-02
5C1 Bushing, 1½ NPT x ¾ NPT
5D
5E
Limit, Honeywell L4006A2015 (SBPT & SBFT)
Well, ¾ NPT x 1½", Honeywell 123890A
41
V72 Thru V79, V713 and V714 WATER BOILERS - TRIM AND CONTROLS
ITEM
NO.
DESCRIPTION
Part No.
V72 V713 V73 V714 V74 V75 V76 V77 V78 V79
V72 Thru V79, V713 and V714 WATER BOILERS - TRIM AND CONTROLS (See Page 42 for Illustration)
1. DRAFT REGULATOR
1A
1B
DR-6 Draft Regulator
DR-7 Draft Regulator
8116029
8116001
1
1
1
1
1
1
1
---- ---- ----
---- ---- ---- ---- ---- ---- ----
1
1
1
2. INSTRUCTION ENVELOPE CONTAINING:
2A
2B
Installation and Operating Instructions
8142711
81460135
81460061
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Limited Warranty Mailer (Water
Boilers)
2C I=B=R Pamphlet
3. CONTROLS
Honeywell L8148A1090 Hi Limit, Circ. 80160449U
1
1
1
1
1
1
1
1
1
1
Relay (WB)
3A
--OR --
Honeywell L8124C1102 Hi & Lo Limit, 80160406U
Circ. Relay (WBT)
----
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Honeywell #123870A Immersion Well,
80160426
¾NPT x 1½ Insulation (WB)
3B
-- OR --
Honeywell #123872A Immersion Well,
80160497 ----
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
½NPT x 3" Insulation (WBT)
Honeywell R4184D (1027/1001)
Protectorelay
3C
80160473
1
4. CIRCULATOR & PIPING (Packaged Boiler Only)
4A
4B
Circulator, Taco 007F (position 2)
Gasket, Taco "00" Series Circulator
8056007
806602006
806602014
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
4C Circulator Flange, 1½"NPT
Cap Screw, Hex Head, 7/16" -14 x
4D
80861301
4
4
4
4
4
4
4
4
4
4
1½"
4E
4F
Hex Nut, 7/16" - 14
80860406
806600011
806601003
806600006
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
4
1
1
1
Nipple, 1½"NPT x18"
4G Tee, 1½" x ¾" x 1½"NPT, Black
4H Nipple, 1½"NPT x 3"
5. MISCELLANEOUS WATER TRIM
Relief Valve, ¾"NPT, F/F 30 LB,
5A
81660319
806600221
8056169U
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Conbraco 10-408-05
5B
Nipple, ¾"NPT x 8"
Te m p/ Pr es su re Gau ge, 2½" Dia.,
5C
ENFM #41042.5210
Drain Cock, ¾"NPT Short Shank
5D
5E
806603011
806603515
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
(WB and WBT), Conbraco #31-606-02
Plug, Square Head, 1½"NPT
(Packaged)
Reducing Bushing, 1½" x ¾"NPT
80660507
(Knockdown)
43
Beckett AFG Burner
BECKETT OIL BURNER PART NOS. FOR V7 SERIES BOILERS
NOTE: When ordering parts always give the serial and model numbers shown on the boiler and burner. Also
provide the name of the part(s) and part number as listed below.
Boiler Model
V72
V713
V73
V714
V74
V75
V76
V77
V78
V79
Air Tube Combination
Beckett's Spec No.
Air Band
AFG70MB AF72YH
AF44XN
AF72YY
AF44WH
AF44RA
AF44XO AF72WK AFG50MD AFG50MD
BCB6111 BCB6119 BCB6112 BCB6120 BCB6113 BCB6114 BCB6115 BCB6116 BCB6117 BCB6118
3492
4150
4198
3709
4198
2999
2454
5880
3666
5636
149
3492
4150
4198
3709
4198
2999
2454
5880
3666
5636
149
3492
4150
4198
3709
4198
2999
2454
[1]
3492
4150
4198
3709
4198
2999
2454
---
3492
4150
4198
3709
4198
2999
2454
[1]
3492
4150
4198
3709
4198
2999
2454
---
3492
4150
4198
3709
4198
2999
2454
---
3492
4150
4198
3709
4198
2999
2454
---
3492
4150
4198
3709
4198
2999
2454
---
3492
4150
4198
3709
4198
2999
2454
---
Air Band Nut
Air Band Screw
Air Shutter
Air Shutter Screw
Blower
Coupling
Low Firing Rate Baffle
Bulkhead Knurled Locknut
Connector Tube Assembly
Electrode Clamp
Electrode Clamp Screw
Electrode Insulator Assembly
Spider Spacer Assembly
Escutcheon Plate
Adjusting Plate Assembly
Head
3666
5636
149
3666
5636
149
3666
5636
149
3666
5636
149
3666
5636
149
3666
5636
149
3666
5636
149
3666
5636
149
4219
5780
5503
3493
---
4219
5780
5503
3493
---
4219
5780
5503
3493
---
4219
5780
5503
3493
---
4219
5780
5503
3493
---
4219
5780
5503
3493
---
4219
5780
5503
3493
---
4219
5780
5503
3493
---
4219
5780
5503
---
4219
5780
5503
---
5941
5913
4221
31498
5877
2456
213
5941
5913
4221
31498
5877
2456
213
5912
4221
31498
5877
2456
213
360003 [4] 360004 360006 [5] 360004 [6] 360006 [7] 360012 360016
Head Screws
4221
31498
5877
4221
31498
5877
4221
31498
5877
4221
31498
5877
4221
31498
5877
4221
31498
5877
2456
213
4221
31498
5877
2456
213
Flange Gasket
AFG Housing
Motor
2456
2456
2456
2456
2456
Nozzle Adapter
213
213
213
213
213
Nozzle Line Electrode Assembly NL72BN
NL72YH
2460
NL44YH
2460
NL72YY
2460
NL44WP
2460
NL44YB
2460
NL44X0 NL72WK NL50MD
NL50MD
2460
3383P
51771
4217
4292
51304
10251
5770
7006
21789
Pump
2460
3384
2460
3383P
51771
4217
2460
None
51771
4217
2460
3383P
51771
4217
Static Plate
3384
[2] 3384
51771
4217
3384
[3] 3383P
51771
4217
3384
Ignitor
51771
4217
51771
4217
51771
4217
51771
4217
Ignitor Hinge Screw
Ignitor Holding Screw
Ignitor Gasket Kit
Wire Guard
4292
4292
4292
4292
4292
4292
4292
4292
4292
51304
10251
5770
51304
10251
5770
51304
10251
5770
51304
10251
5770
51304
10251
5770
51304
10251
5770
51304
10251
5770
51304
10251
5770
51304
10251
5770
Junction Box
Flame Detector
Oil Solenoid Valve
7006
7006
7006
7006
7006
7006
7006
7006
7006
21789
21789
21789
21789
21789
21789
21789
21789
21789
[1] 5880 in V73R, V73M and V74R [2] 3912 in V73M and V73R [3] 3384 in V74M and V74R [4]360000 in V73R; 360003 in V73M
[5] 360003 in V74R and V74M [6] 360003 in V75R; 360006 in V75M [7] 360006 in V76R; 360012 in V76M
45
Print word document
46
47
|
Blaupunkt LAS VEGAS 7 645 650 310 User Manual
Bushnell Binoculars 190125 User Manual
Canon Camcorder VIXIA HF630 User Manual
Casio Fx 115esplus Scientific Calculator fx115ESPlus User Manual
Directed Audio 6550 User Manual
Earthquake Sound DBXI 15 User Manual
HP (Hewlett Packard) Hewlett Packard Car Amplifier 8447F User Manual
Infinity Systems Inc Car Speaker BU 2 User Manual
Jensen Phase Linear SD1413 User Manual
Jensen POWER 880 User Manual